Findings Sample
Our written reports translate complex physical observations into prioritized, actionable compliance records. Each finding is catalogued with exact locations, specific hazard descriptions, and clear operational priorities.

Structure of the Findings Report
Structure
Within 7 working days of the walk-through, clients receive a structured findings document edited by Ines Moreau. Each report opens with an executive overview summarizing overall facility compliance, followed by an itemized findings register. Individual findings are assigned unique reference codes, precise room locations, direct physical observations, and photographic evidence. We record observed non-compliance against standard fire precaution rules, such as uninspected suppression cylinders, wedged fire doors, or blocked directional signs. The document concludes with an actionable management summary outlining clear operational corrections that facility managers can coordinate directly with their maintenance contractors.
How Are Risk Priorities Defined in the Report?
Priority
We categorize all observed issues using three distinct priority levels to help duty holders allocate maintenance resources effectively. Immediate designates critical hazards requiring immediate intervention, such as locked escape exits during occupied hours, impaired kitchen suppression discharge lines, or missing primary alarm sounders. Urgent addresses significant compliance failures that require prompt resolution within defined statutory timelines, including overdue extinguisher inspections, unrecorded evacuation drills, or compromised fire-door seals. Advisory identifies minor advisory items or maintenance improvements, such as damaged exit directional signage or low-level housekeeping clutter near electrical distribution cupboards.
P1
A hazard to put right before the premises are next occupied.
Immediate
P2
A failing to fix within a time agreed with the duty holder.
Urgent
P3
A minor item to fold into routine maintenance.
Advisory
Representative Findings Register Excerpt
Register
A typical report register includes concrete observations drawn directly from site inspections. For example, item F-01 notes a blocked chemical suppression nozzle directly above a commercial cooking range, requiring realignment to cover the fryer surface. Item F-02 records palletized carton storage stacked within 300 mm of ceiling sprinkler deflector plates in a warehouse aisle, obstructing design spray patterns. Item F-03 documents an internal fire door held open with a wooden wedge in a medical consulting hallway, neutralizing compartmentation. Each entry provides unambiguous descriptions allowing property owners to rectify issues without guesswork.
| Ref | Place | What we saw | Priority |
|---|---|---|---|
| F-01 | Main kitchen canopy | Discharge nozzle turned away from the deep fryer. | Immediate |
| F-02 | North warehouse, aisle 3 | Stacked pallets within 300 mm of a sprinkler deflector. | Urgent |
| F-03 | First-floor clinic corridor | Self-closing fire door latch not seating in its frame. | Advisory |
| F-04 | Food hall, fryer station | Manual pull station partly hidden behind a shelving unit. | Urgent |
| F-05 | Loading bay | Final exit door chained shut during occupied hours. | Immediate |
| F-06 | South stairwell | No emergency lighting test entries for six months. | Urgent |
| F-07 | Office, second floor | Fire door held open with a rubber wedge. | Urgent |
| F-08 | Cold store, dock side | Extinguisher service tag two years out of date. | Urgent |
| F-09 | Clinic storeroom | Escape route narrowed by boxed supplies. | Immediate |
| F-10 | Main corridor | Exit direction sign faces the wrong way after repainting. | Advisory |
| F-11 | Workshop | Hose reel cabinet door sticks and needs both hands. | Advisory |
| F-12 | Reception | Staff drill log has no entry in the last year. | Advisory |